6.4. Fixing surface area

The unit's excessive weight requires a firm base for support, completely horizontal and leveled, assuring proper
water drainage and avoiding water accumulation.
To perform the installation calculations it is necessary to take into account the loads that affect the environment
conditions, according to the country's regulations.
The following figures only show the vertical loads on each of the supports. The minimum number of supports is six,
as well as two additional optional ones. They differ depending on whether the inverter has the bottom cover kit:
Without bottom cover
2189 N
1930 N
i
i = 11.81 in (300 mm)
Footings
Compulsory support points
Optional support points
Area sealed for DC supply
46
43.58 in (1,107 mm)
4025 N
39.29 in (998 mm)
4363 N
i
33.11 in (841 mm)
107.82 in (2,739 mm)
ABK2027IQE01_A - Installation and Operation Manual
Preparation for installing the unit
Top view
3225 N
3010 N
i