10.2.2. Three units connected to the same transformer winding

When connecting three units to the same transformer winding, the grounding of the system must be unique and
shared, as otherwise there could be currents flowing through the different ground connections.
Each inverter will be equipped with the following elements to carry out the configuration:
One independent input with 1500 V fuse to connect the grounded fuses.
One CAN communication cable for connecting the communications of the inverters.
Once the units have been installed, the following connections are performed:
1.
Connect the grounded pole of the three units through 35 mm
insulation. This connection can be done through the cable grommets provided in the bases of the units in
question.
Inverter 1
78
-INV1 (-TSGND)
-Rfin
-X26
1A
2A
3A
4A
1B
2B
3B
4B
1C
2C
3C
4C
1D
2D
3D
4D
-INV1 (-TSGND)
-Rfin
-X26
1A
2A
3A
4A
1B
2B
3B
4B
1C
2C
3C
4C
Connection of the PV array grounding kit [optional]
-INV2
-X26
1A
1B
1C
1D
-Rfout
-INV2
White
Brown
-X26
1B
1C
1D
-Rfout
-CAN_1
section cables with 1000/1500 V
2
Inverter 2
ABK2027IQE01_A - Installation and Operation Manual
2A
3A
4A
2B
3B
4B
2C
3C
4C
2D
3D
4D
Yellow
Green
2B
3B
4B
2C
3C
4C
2D
3D
4D
Inverter 3