Noise Contamination; Ventilation; Mounting And Anchorage Surface - Ingeteam Ingecon mWind Interface Installation Manual

Table of Contents

Advertisement

Ingeteam Power Technology, S.A.

2.1.6. Noise contamination

When operating, the equipment makes a slight buzzing noise.
Do not locate the equipment in an occupied room, or on lightweight supports that could amplify this
buzzing noise. The mounting surface must be firm and adequate for the weight of the equipment.

2.1.7. Ventilation

The equipment is designed to be cooled by natural convection.
There must be a 30 cm obstacle-free area above the equipment and 20 cm around the base. This is to ensure that
the inverter cooling system operates correctly.
Facilitate the circulation of incoming and outgoing air through the ventilation grids.

2.1.8. Mounting and anchorage surface

To guarantee correct heat dissipation and airtightness, the equipment must be mounted on a perfectly vertical wall
or, failing this, with a maximum angle of inclination of +10º or -10º to the vertical.
The equipment should be mounted on a solid wall that will allow holes to be drilled and the insertion of lag screws
and rawl plugs capable of withstanding the weight of the equipment.
The following figure provides the measurements in millimetres for drilling the holes.
12
Installation manual
AAY2000IKI06