Device parameters and interfaces
8.1.7.20 Module 19: Service
Description
The "service" function is used to reset the parameter set of the BPS 34 to default settings.
This reset only occurs directly in the BPS 34. After the reset function has been activated, the
device carries out a reset and is freshly configured on the PROFIBUS. This results in the
reactivation of all modules and parameter settings selected in the PROFIBUS project.
Parameter
none
Input data
Input data
Description
a
Shows the state of the reset to
factory settings
Status byte
Input data length: 1 byte
Output data
Output
Description
data
b
Reset of parameters to factory
Factory
settings.
settings
Output data length: 1 byte
Notice!
The preset function (module 3) must be retaught following a reset.
76
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Rel.
Data
Value range
addr.
type
0x00: Not active or suc-
unsign
cessfully concluded
0
8
0xFF: Reset active
0xF1: EEPROM access error
Rel.
Data
Value range
addr.
type
0 -> 1: Reset the parameters
0.0
Bit
1 -> 0: Standard operation
BPS 34
Leuze
electronic
Default
Unit
CR to
module
0x00
Default
Unit
CR to
module
0
Leuze electronic

Advertisement