Leuze electronic BPS 34 Technical Description page 58

Barcode positioning system for the profibus dp
Hide thumbs Also See for BPS 34:
Table of Contents

Advertisement

Device parameters and interfaces
8.1.7.5 Module 5: Offset value
Notice!
Underlined in the CR column are the modules which must be activated in addition to the cur-
rent module.
Description
This module adds an offset value to the tape value.
Parameter
Parameter
Description
a
Offset
Offset value added to tape value
value in
[mm]
Parameter length: 4 byte
Notice!
If module 3 "Static preset" or module 4 "Dynamic preset" is activated and, as a result, a new
value assigned to the tape value, the offset function no longer affects the position value. The
offset is not reactivated until the preset function (static and dynamic) is cancelled. The offset
value is entered in mm. When entering the offset value, the scaling in module 6 must be tak-
en into account.
Hex coding of module 5 "Offset value"
The value listed in the table shows the hex coding of the default settings.
09
Input data
none
Output data
none
56
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Rel.
addr.
0
00 00 00 00
Data
Value range
type
sign32 -10'000'000 ... 10'000'000
BPS 34
Leuze
electronic
Default
Unit
CR to
module
0
mm
Leuze electronic