Leuze electronic BPS 34 Technical Description page 55

Barcode positioning system for the profibus dp
Hide thumbs Also See for BPS 34:
Table of Contents

Advertisement

Leuze
electronic
8.1.7.3 Module 3: Static preset
Notice!
Underlined in the CR column are the modules which must be activated in addition to the cur-
rent module.
Description
With this module, a preset value can be defined which the BPS 34 outputs following a teach
event. Defined as a teach event is either bit 0.0 in the output data of this module or a
switching input function. After reading in the teach event, the current position value is
replaced by the preset value and the position value now calculated and output on the basis
of the preset value. The preset remains stored in the BPS 34 and remains active even
following a new start. In order for the BPS 34 to again output the position value without the
preset, bit 0.1 in the output data must be set.
Notice!
In the event of a device change, the preset value is retained in the MS 34 10x. The activation
of the preset value (preset teach) at the intended position is not necessary.
Parameter
Parameter
a
New position value after teach
Static pre-
event
set value in
[mm]
Parameter length: 4 byte
Notice!
The preset value is always entered in units of mm, independent of the resolution setting
(module 2). The scaling factor (module 6) has no effect on the static preset value.
Hex coding of module 3 "Static preset"
The value listed in the table shows the hex coding of the default settings.
06
Leuze electronic
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Description
Rel.
addr.
0
00 00 00 00
Device parameters and interfaces
Data
Value range
type
unsign
0 ... 10'000'000
32
BPS 34
Default
Unit
CR to
module
12c
7g
0
mm
or
3b
53