Diagnostics and troubleshooting
9
Diagnostics and troubleshooting
9.1
General causes of errors
Error
LED MS 34 10x =
"off"
LED MS 34 10x =
"flashes red"
LED MS 34 10x =
"red continuous light"
(no communication via
PROFIBUS)
LED MS 34 10x =
"orange continuous
light"
Position error
9.2
PROFIBUS errors
Error
Sporadic errors at the
PROFIBUS
92
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Possible error cause
• No supply voltage connected to
the device.
• Device not yet recognised by the
PROFIBUS
Notice: The LED remains off until
the BPS 34 is recognised by the
PROFIBUS. Only after the
PROFIBUS has addressed the
BPS 34 for the first time do the
following status descriptions
apply.
• Error on the PROFIBUS.
• Incorrect wiring.
• Wrong termination.
• Incorrect PROFIBUS address set.
• PROFIBUS deactivated.
• Incorrect configuration.
• Parameter-memory overflow in
the control.
• Service operation active.
• No barcode tape present.
• Scanner positioned in total reflec-
tion
• Scanner not properly mounted
Possible error cause
• Incorrect wiring.
• Wrong termination.
• Electromagnetic influences.
• Overall network expansion
exceeded.
BPS 34
Leuze
Measures
❏
Check supply voltage.
❏
Check PROFIBUS settings.
❏
Reset device
(switch voltage on/off).
❏
Check wiring.
❏
Check termination.
❏
Check PROFIBUS address.
❏
Activate PROFIBUS interface.
❏
Check configuration of the device in the con-
figuration tool.
❏
Reduce number of modules.
❏
Set the service switch in MSD 1 101 to
"Operation"
❏
Check positioning of barcode tape.
❏
Change the angle of the scanning beam by
tilting the BPS 34.
❏
Check mounting.
Measures
❏
Check wiring.
❏
Check termination.
❏
Check shielding.
❏
Check grounding concept and connection to
FE.
❏
Check max. network expansion as a func-
tion of the set baud rate.
electronic
Leuze electronic