8.1.7.15 Module 14: Static position limit value 1
Description
The limit value function compares the output position value with a position stored during
configuring. If the value is above or below the limit value, the limit value status 1 (module 12)
is set and, if configured, the switching output (module 8) is appropriately set.
Parameter
Parameter
a
Parameter activates limit
Limit value
value checking.
mode 1
Condition for the signal
b
change of the switching out-
Switching
put/status bit.
mode 1
c
Relative offset of switching
Hysteresis 1
point
in [mm]
d
Limit value is compared to the
Limit value 1
current position value.
in [mm]
Parameter length: 8 byte
Hex coding of module 14 "Static position limit value 1"
The value listed in the table shows the hex coding of the default settings.
0D
Input data
none
Output data
none
Notice!
With this module, the settings for the Preset (module 3), Offset (module 5) and Scaling
(module 6) modules must be taken into account.
Leuze electronic
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Description
Rel.
addr.
0
1
2
4
00
00
00 00
Device parameters and interfaces
Data
Value range
type
unsign
0: Off
8
1: On
unsign
0: Value greater than limit
8
1: Value less than limit
unsign
0 ... 65'535
16
sign32 -10'000'000 ... 10'000'000
00 00 00 00
BPS 34
Default
Unit
CR to
module
0
7 g
0
8d
0
mm
0
mm
12e
71