Commissioning steps at a glance
Connecting the PROFIBUS
The PROFIBUS is connected via DP IN or, in the case of a continuing network, via DP OUT.
If DP OUT is not used, the PROFIBUS must be terminated at this point with an M 12 termi-
nator plug (see chapter 10.4 "Accessory termination").
DP OUT
VCC 1
Socket
(B-coded)
Figure 3.3:
Setting the PROFIBUS address
The PROFIBUS address must be set in the MS 34 10x connector plug hood. The correct
address setting on the PROFIBUS network is indicated by the green LED on the MS 34 10x.
Figure 3.4:
10
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Socket
(A-coded)
MSD
VIN
TXD
2
/INT
3
/SERV
1
5
7
GND
6
SDA
A (N)
2
GND
3
4
PE
B (P)
BPS 34 with MS 34 103/MS 34 105 - Connections DP IN and DP OUT
Slide switch for the hundreds (marked with 10
Rotary switch for the tens (marked with 10
Rotary switch for the single digits (marked with 10
View of the inside of the MS 34
SW IN/OUT
RXD
4
VOUT
SCL
DP IN
A (N)
2
GND 3
VCC
1
4
PE
B (P)
Plug
(B-coded)
Connector to the BPS 34
BPS 34
Leuze
electronic
Socket
(A-coded)
SWOUT
2
GND
1
3
4
PE
PWR IN
SWIN
SWOUT
3
GND
PE
SWIN
Plug
(A-coded)
2
)
1
)
0
)
Position of the slide
switch:
Top
address
100 - 126
Bottom
address
1 - 99
Leuze electronic
2
VIN
1
4