Table 2-2
Coral
System Cabinet Heat
Dissipation
2-4
Hardware Installation Procedure
7. Verify that the installation area is located no closer than 20 feet (6.1m) from
electric devices which produce large electro-magnetic fields or high levels of
radio frequency energy. Possible sources are radio transmitters, electric arc
welding machines, copying machines, electric motors, elevators, refrigeration
units, power transformers, electric load centers, and main circuit breaker
panels.
8. Verify that the installation area provides reasonable security to the system.
Room construction should include solid, reinforced walls and a locking door.
The Coral system, and the service it provides to users, represents a substantial
investment. During an emergency, reliable service may be crucial in protecting
lives and property. Access to the system should be limited and controlled to
prevent unauthorized tampering. The system uses hazardous working voltages
and extremely high short circuit currents, and the area must be protected
against damage by, and injury to, unqualified personnel.
Coral System Cabinet
Main with 2 Peripheral Shelves
Main with 3 Peripheral Shelves
Expansion: 2 Peripheral Shelves
Expansion: 3 Peripheral Shelves
Expansion: 4 Peripheral Shelves
Heat Dissipation (BTU/hr.)
Nominal
Maximum
2,048
3,755
3,072
5,461
1,878
3,413
2,817
5,120
3,756
6,826
Coral FlexiCom 6000 Installation Manual