8.33 L41, current transformer upstream of main switch

8.33
L41, current transformer upstream of main switch
Availability of option
This option is available for the following S120 Cabinet Modules:
● Line Connection Modules
Description
If current transformers are used for measuring or monitoring purposes, they are installed in
the Line Connection Modules with option L41. The current transformers are installed
upstream of the main breaker in all three line phases of the infeed.
The transformers have an accuracy class of 1.0. The secondary current is 1 A maximum.
The measuring connections for the current transformers are routed in the Line Connection
Module to terminal block -X60.
Transformation ratio of the current transformer in the Line Connection Module
The assignment of the order numbers of the Line Connection Modules to the transformation
ratios of the current transformers is shown in the following table.
Table 8- 56
Order no.
6SL3700-0LE32-5AA3
6SL3700-0LE34-0AA3
6SL3700-0LE36-3AA3
6SL3700-0LE38-0AA3
6SL3700-0LE41-0AA3
6SL3700-0LE41-3AA3
6SL3700-0LE41-6AA3
6SL3700-0LE42-0AA3
6SL3700-0LE42-0BA3
6SL3700-0LE42-5BA3
6SL3700-0LE43-2BA3
6SL3700-0LG32-8AA3
6SL3700-0LG34-0AA3
6SL3700-0LG36-3AA3
6SL3700-0LG38-0AA3
6SL3700-0LG41-0AA3
6SL3700-0LG41-3AA3
6SL3700-0LG41-6AA3
6SL3700-0LG42-0BA3
6SL3700-0LG42-5BA3
6SL3700-0LG43-2BA3
496
Transformation ratios of the current transformers
V
IN
380 to 480 V AC, 3-phase
380 to 480 V AC, 3-phase
380 to 480 V AC, 3-phase
380 to 480 V AC, 3-phase
380 to 480 V AC, 3-phase
380 to 480 V AC, 3-phase
380 to 480 V AC, 3-phase
380 to 480 V AC, 3-phase
380 to 480 V AC, 3-phase
380 to 480 V AC, 3-phase
380 to 480 V AC, 3-phase
500 to 690 V AC, 3-phase
500 to 690 V AC, 3-phase
500 to 690 V AC, 3-phase
500 to 690 V AC, 3-phase
500 to 690 V AC, 3-phase
500 to 690 V AC, 3-phase
500 to 690 V AC, 3-phase
500 to 690 V AC, 3-phase
500 to 690 V AC, 3-phase
500 to 690 V AC, 3-phase
Transformation ratio
400/1
400/1
800/1
800/1
2000/1
2000/1
2000/1
4000/1
4000/1
4000/1
4000/1
400/1
800/1
800/1
800/1
2000/1
2000/1
2000/1
4000/1
4000/1
4000/1
Cabinet Modules
Manual, 03/2013, A5E03263538A