Smart Line Modules; General Information; Description - Siemens SINAMICS S120 Manual

Cabinet modules
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Cabinet Modules

5.3 Smart Line Modules

5.3
Smart Line Modules
5.3.1

General information

Hazardous electrical voltage
Hazardous voltages are present in certain parts of this equipment during operation of the
cabinet unit.
Only qualified personnel may work on the cabinet.
Such personnel must be thoroughly familiar with all the warnings and maintenance
procedures for the cabinet described in the documentation provided.
The successful and safe operation of this cabinet unit is dependent on correct transport,
proper storage and installation, as well as careful operation and maintenance.
National safety regulations must be observed.
5.3.2

Description

Note
Additional information
Refer to the layout diagrams (AO) and circuit diagrams (SP) provided on the customer DVD
supplied with the device for the arrangement of components and interfaces, and for wiring.
Smart Line Modules are infeed/regenerative feedback units. Like the Basic Line Module,
they supply energy to the connected Motor Modules, but unlike the Basic Line Module, they
can feed back regenerative energy. The infeed occurs over a diode jumper, while stable,
line-commutated regenerative feedback takes place via IGBTs with 100% continuous energy
regeneration.
Under full load, the DC link voltage is higher than the rms value of the rated line voltage by a
factor of 1.30, and under partial load by a factor of 1.32.
Smart Line Modules are suitable for connection to supply systems grounded at the neutral
point (TN, TT) and non-grounded (IT) supply systems. The following voltages and power
ratings are available:
Line voltage
380 to 480 V AC, 3-phase
500 to 690 V AC, 3-phase
The power rating can be increased by connecting Smart Line Modules in parallel.
168
DANGER
Rated power
250 ... 800 kW
450 ... 1400 kW
Manual, 03/2013, A5E03263538A
Cabinet Modules

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents