Cabinet Modules
5.8 Auxiliary Power Supply Modules
5.8.3

Fuse switch disconnector (-Q1)

The customer feeds power to the Auxiliary Power Supply Module on the fuse switch
disconnector (-Q1). The plant-side power demand indicated in the table "Technical data"
varies according to the version of the Cabinet Module used.
5.8.4
Transformer (-T2) for generating the auxiliary voltage 230 V AC
A transformer is incorporated to generate the 230 V AC, 2-phase voltage. This voltage is
made available in order to supply the auxiliary power system and the SITOP power supply.
When delivered, the taps are always set to the highest level. The line-side terminals of the
transformer may need to be reconnected to the existing line voltage.
The line voltage assignments for making the appropriate setting on the transformer for the
internal power supply are indicated in the following table.
Note
Reconnecting the terminals according to the actual line voltage
The terminals must be reconnected to the actual line voltage so that the 230 V AC, 2-phase
voltage required in the system is provided correctly.
Hazardous electrical voltage
Reconnect the terminals only when the cabinet unit is disconnected from the power supply.
Table 5- 53
260
WARNING
Assignment of the available line voltage for generating the 230 V AC, 2-phase voltage
Tap
380 V
400 V
415 V
440 V
460 V
480 V
500 V
525 V
550 V
575 V
600 V
660 V
690 V
Taps of voltage adaptation transformer (T2) L
3 – 4
2 – 4
1 – 4
3 – 5
2 – 5
1 – 5
3 – 6
2 – 6
1 – 6
3 – 7
2 – 7
3 – 8
1 – 8
– L
A
B
Cabinet Modules
Manual, 03/2013, A5E03263538A