X521: Analog Inputs; S5 Current/Voltage Changeover Switch For Analog Inputs; Table 3-16 Terminal Block X521; Table 3-17 Current/Voltage Selector S5 - Siemens SINAMICS S120 Equipment Manual

Control units and additional system components
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

3.3.3.8

X521: Analog inputs

Table 3-16
Terminal block X521
Terminal
1
2
3
4
5
6
7
8
Max. connectable cross-section: 1.5 mm²
Type: Screw terminal 1 (see Appendix A)
1) AI: analog inputs; P10/N10: auxiliary voltage; M or GND: ground reference
Caution
A current of 40 mA must not be exceeded during current measurement.
The common-mode range must not be infringed, that is, the analog differential voltage
signals can have a maximum offset voltage of +/- 30 V with respect to the ground potential.
If the range is infringed, incorrect results may occur during analog/digital conversion.
3.3.3.9

S5 current/voltage changeover switch for analog inputs

Table 3-17
Current/voltage selector S5
Equipment Manual Control Units and Additional System Components
Equipment Manual, (GH1), 12/2004 Edition, 6SL3097-2AH00-0BP1
Name
1)
AI 0+
AI 0-
AI 1+
AI 1-
P10
M
N10
M
Switch
S5.0
S5.1
Technical specifications
You can set the following input signals using the
appropriate parameters:
Voltage: -10 V to 10 V; R
Current 1: 4 mA to 20 mA; R
Current 2: -20 mA to 20 mA; R
Current 3: 0 mA to 20 mA; R
Resolution: 12 bits
Auxiliary voltage:
P10 = 10 V
N10 = -10 V
Continued-short-circuit-proof
Function
Selector voltage (V)/current (I) Al0
Selector voltage (V)/current (I) Al1
Additional System Components
3.3 Terminal Module 31 (TM31)
= 100 kΩ
i
= 250 Ω
i
= 250 Ω
i
= 250 Ω
i
3-21