Drive-Cliq Interfaces X400, X401, X402 - Siemens SINAMICS S120 Manual

Cabinet modules
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Cabinet Modules
5.2 Basic Line Modules
Risk of electric shock!
Only temperature sensors that meet the safety isolation specifications stipulated in
EN 61800-5-1 may be connected to terminals "+Temp" and "-Temp". If safe electrical
separation cannot be guaranteed (for linear motors or third-party motors, for example), a
Sensor Module External (SME120 or SME125) must be used.
Failure to observe these instructions can result in electric shock!
Note
Connectable sensor
The following sensors can be connected to the temperature sensor connection:
KTY84-1C130 / PTC.
NOTICE
Use shielded cables
The temperature sensor connection must be shielded. The shielding must be attached to
the shield support of the module.
Note
KTY temperature sensor connected with the correct polarity
The KTY temperature sensor must be connected with the correct polarity.
If the polarity is reversed, the sensor will not be able to detect if the motor overheats.
5.2.3.4

DRIVE-CLiQ interfaces X400, X401, X402

Table 5- 14
DRIVE-CLiQ interfaces X400, X401, X402
PIN
1
2
3
4
5
6
7
8
A
B
Blanking plate for DRIVE-CLiQ interfaces (50 pcs.) order number: 6SL3066-4CA00-0AA0
162
DANGER
Signal name
TXP
TXN
RXP
Reserved, do not use
Reserved, do not use
RXN
Reserved, do not use
Reserved, do not use
+ (24 V)
M (0 V)
Technical specifications
Transmit data +
Transmit data -
Receive data +
Receive data -
24 V power supply
Electronics ground
Cabinet Modules
Manual, 03/2013, A5E03263538A