Siemens SINAMICS S120 Manual page 352

Cabinet modules
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Diagnostics
7.2 LEDs on the CU320-2 DP Control Unit
LED
Color
OPT
(OPTION)
Green
Red
RDY and
Red
DP
RDY and
Orange
OPT
350
State
Flashing
Cyclic bus communication has been interrupted
light
or could not be established
2 Hz
Off
The electronics power supply is missing or lies
outside the permissible tolerance range.
Component is not ready.
Option Board not installed or no associated drive
object has been created.
Steady light Option Board is ready.
Flashing
Depends on the option board used.
light
0.5 Hz
Steady light At least one fault is present in this component.
Option board not ready (e.g. after switch on).
Flashing
Bus error - communication has been interrupted
light
2 Hz
Flashing
Firmware update in progress for connected
light
Option
0.5 Hz
Board CBE20
Description, cause
Remedy
Remove the fault
Check power supply and/or
component
Remedy and acknowledge
fault
Remove the fault
-
Cabinet Modules
Manual, 03/2013, A5E03263538A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents