Table 8- 15
Line supply voltage range
Table 8- 16
Line supply voltage range
Note
Consequences when using an unmatched transformer
If the terminals are not reconnected to the actual supply voltage, the internal power supply
will not be correct.
Cabinet Modules
Manual, 03/2013, A5E03263538A
8.16 K76, auxiliary voltage generating unit in the Line Connection Module
Line voltage assignments for the internal power supply
(380 to 480 V 3 AC)
342 ... 390 V
391 ... 410 V
411 ... 430 V
431 ... 450 V
451 ... 470 V
471 ... 528 V
Line voltage assignment for the internal power supply (500 to 690 V AC, 3 phase)
450 ... 515 V
516 ... 540 V
541 ... 560 V
561 ... 590 V
591 ... 630 V
631 ... 680 V
681 ... 759 V
Tap
Taps of the voltage matching transformer
380 V
400 V
415 V
440 V
460 V
480 V
Taps of the voltage matching transformer
Tap
500 V
525 V
550 V
575 V
600 V
660 V
1 to 14, terminals 12 and 13 are jumpered
690 V
1 to 15, terminals 12 and 13 are jumpered
(-T10) LH1 – LH2
1 – 2
1 – 3
1 – 4
1 – 5
1 – 6
1 – 7
(-T10) LH1 – LH2
1 – 8
1 – 9
1 – 10
1 – 11
1 – 12