Maintenance and servicing
6.5 Forming the DC link capacitors
● 6 incandescent lamps 230 V / 100 W for a line voltage of 500 to 690 V 3 AC, where 2
● Various small components, such as lamp sockets, cable 1.5 mm
Forming circuit for Line Modules
Note
Forming the Line Modules
Voltage must be supplied to Line Modules via a connected Motor Module and the associated
DC link.
Figure 6-32
344
incandescent lamps must be connected in series in each supply phase.
Alternatively, use 3 resistors of 1 kΩ / 160 W each (e.g. GWK200J1001KLX000 from
Vishay) instead of the incandescent lamps.
CAUTION
Install lamp sockets so that they are insulated
For a line voltage of 500 to 690 V 3 AC, the two lamp sockets connected in series must
be insulated and protected from touch, because the insulation of the sockets is not
designed for this high voltage.
Forming circuit for Line Modules
, etc.
2
Cabinet Modules
Manual, 03/2013, A5E03263538A