Risk of fire and damage to equipment due to short-circuit/ground fault
The cables to the braking resistor must be routed so that a ground fault or short circuit can
be ruled out. A ground fault can result in fire with the associated smoke.
Protect the cables from mechanical damage.
Comply with local installation regulations that enable this fault to be ruled out.
In addition, apply one of the following measures:
Use cables with double insulation.
Maintain adequate clearance, using spacers, for example.
Route the cables in separate cable ducts or pipes.
Note
Maximum cable length
A maximum cable length of 300 m is permissible between the Central Braking Module and
the braking resistor.
Note
Installation notes
Sufficient space must be available for dissipating the energy converted by the braking
resistor.
A sufficient distance from flammable objects must be ensured.
The braking resistor must be installed as a free-standing unit.
Objects must not be placed on or anywhere above the braking resistor.
The braking resistor should not be installed underneath fire-detection systems, since these
could be triggered by the resulting heat.
For outdoor installation, a hood should be provided to protect the braking resistor from
precipitation (in accordance with degree of protection IP21).
Cabinet Modules
Manual, 03/2013, A5E03263538A
WARNING
Cabinet Modules
5.7 Central Braking Modules
249