8.23 L00, use in the first environment according to EN 61800-3, Category C2 (TN/TT systems)
Note
Combining a line filter and line reactor
The optional line filter must always be combined with a line reactor, otherwise it cannot
achieve its full filter effect.
Note
EMC shield bus
To allow the power cable shield to be connected in conformance with EMC requirements, an
additional EMC shield bus (M70 option) is factory fitted at the converter input and output.
Note
It is not possible to combine insulation monitoring and line filter
It is not possible to use the insulation monitoring function (option L87) in conjunction with the
optional line filter.
NOTICE
Maximum permissible motor cable length
The maximum permissible total motor cable length when using the line filters in conjunction
with Basic Line Modules is 100 m.
The maximum permissible total motor cable length when using the line filter in connection
with Smart Line Modules and Active Line Modules is 300 m.
Shielded motor cables must always be used.
462
Cabinet Modules
Manual, 03/2013, A5E03263538A