Overload Capability - Siemens SINAMICS S120 Manual

Cabinet modules
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Cabinet Modules
5.6 Chassis format Motor Modules
5.6.6

Overload capability

The Motor Modules in the chassis format are equipped with an overload reserve to handle
breakaway torques, for example.
In the case of drives with overload requirements, the appropriate base load current must,
therefore, be used as a basis for the required load.
For overload, the following precondition applies: The drive is operated with its base load
current before and after the overload occurs (a duty cycle duration of 300 s is used as a
basis here).
Small overload
The base load current I
duty cycle period of 300 s.
Figure 5-35
High overload
The base load current I
load cycle period of 300 s.
Figure 5-36
234
is based on a duty cycle of 110 % for 60 s or 150 % for 10 s with a
L
Small overload
is based on a load cycle of 150 % for 60 s or 160 % for 10 s with a
H
High overload
Cabinet Modules
Manual, 03/2013, A5E03263538A