5.2.3.2
Control Interface Module
Figure 5-15
5.2.3.3
X41 EP terminal / temperature sensor connection
Table 5- 13
Terminal strip X41 EP terminals / temperature sensor connection
Terminal
1
2
3
4
Max. connectable cross-section: 1.5 mm
Note
Connection at terminals 1 and 2
24 V DC must be present at terminal 2 and ground at terminal 1 for operation. Pulse
suppression is activated when removed.
Cabinet Modules
Manual, 03/2013, A5E03263538A
Control Interface Module
Function
EP M1 (Enable Pulses)
EP +24 V (Enable Pulses)
- Temp
+ Temp
2
Technical data
Supply voltage: 24 V DC (20.4 ... 28.8 V)
Current consumption: 10 mA
Temperature sensor connection:
KTY84-1C130 / PTC
Cabinet Modules
5.2 Basic Line Modules
161