To activate the interconnection, parameterization (in the expert list) must be carried out as
follows (in this example, it has been assumed that the drive is called "Drive_1" in the project
navigator):
Table 8- 53
Parameterization for the interconnection for "Operation enabled"
Parameterization
(Drive_1) p20161 = 0
(Drive_1) p20158 = (Drive_1) r0863.1
(Drive_1) p20159 = 4000.00
(Drive_1) p20146 = 0
(Drive_1) p20143 = (Drive_1) r20160
(Drive_1) p20144 = 5000.00
(Drive_1) p20048 = 0
(Drive_1) p20046[0] = (Drive_1) r20145
(Drive_1) p20046[1] = (TM31) r4022.9
(Drive_1) p20046[2] = 0
(Drive_1) p20046[3] = 0
(Drive_1) p20032 = 0
(Drive_1) p20030[0] = (Drive_1) r20047
(Drive_1) p20030[1] = (Drive_1) r0863.1
(Drive_1) p20030[2] = 1
(Drive_1) p20030[3] = 1
(Drive_1) p0860[0] = (Drive_1) r20031
(Drive_1) p0852[0] = (TM31) r4022.9
(Drive_1) p0861 = 5000
Cabinet Modules
Manual, 03/2013, A5E03263538A
Description
The "switch on delay 0 (PDE 0)" function block is assigned to run-time
group 0.
Input pulse I of the function block "Switch on delay 0 (PDE 0)" of the drive
is interconnected using the "control contactor" drive signal.
The pulse delay time of function block "Switch on delay 0 (PDE 0) of the
drive is set to 4000.00 ms.
The "Pulse generator 1 (MFP 1)" function block is assigned to run-time
group 0.
Input pulse I of function block "Pulse generator 1 (MFP 1)" is
interconnected with output Q of function block "Switch on delay 0 (PDE
0)".
The pulse duration of the "Pulse generator 1 (MFP 1)" function block is
set to 5000.00 ms.
The "OR 0" function block is assigned to run-time group 0.
Output pulse Q of function block "Pulse generator 1 (MFP 1)" of the drive
is interconnected at input I0 of the "OR 0" function block.
Input signal DI9, terminal X541.3 of TM31 is interconnected at input I1 of
function block "OR 0".
A "0" signal is interconnected at input I2 of function block "OR 0"
A "0" signal is interconnected at input I3 of function block "OR 0".
The "AND 0" function block is assigned to run-time group 0.
Output signal Q of function block "OR 0" of the drive is interconnected at
input I0 of function block "AND 0" of the drive.
The "control contactor" signal of the drive is interconnected at input I1 of
the "AND 0" function block of the drive.
A "1" signal is interconnected at input I2 of function block "AND 0" of the
drive.
A "1" signal is interconnected at input I3 of function block "AND 0" of the
drive.
The output signal of the "AND 0" function block of the drive is used for the
"Line contactor feedback" signal of the drive.
Input signal DI9, terminal X541.3 of TM31 is used for the signal "enable
operation" of the drive.
The monitoring time of the line contactor is set to 5000 ms.
8.31 L34, output-side circuit breaker