8.48 M51, motor reactor terminal connection

8.48
M51, motor reactor terminal connection
Availability of option
This option is available for the following S120 Cabinet Modules:
● Booksize Cabinet Kits
Description
In conjunction with option M77 (version without component support plates and without
additional control components), option L08/L09 (motor reactor / 2 motor reactors in series)
allows the motor cables to be connected directly to the motor reactor.
With option M51, the connection of the motor cable is wired to a customer connection
terminal -X1 (for Double Motor Module: -X1, -X2).
Table 8- 75
Order number
6SL3720-
2TE13-0AB0
2TE15-0AB0
2TE21-0AB0
2TE21-8AB0
1TE13-0AB0
1TE15-0AB0
1TE21-0AB0
1TE21-8AB0
1TE23-0AB0
1TE24-5AB0
1TE26-0AB0
1TE28-5AB0
1TE31-3AB0
1TE32-8AB0
536
Maximum conductor cross-section when using motor reactors for Booksize Cabinet Kits
Power in kW
2 x 1.6
2 x 2.7
2 x 4.8
2 x 9.7
1.6
2.7
4.8
9.7
16
24
32
46
71
107
Maximum connection cross
section
6 mm²
6 mm²
6 mm²
6 mm²
6 mm²
6 mm²
6 mm²
6 mm²
6 mm²
16 mm²
16 mm²
35 mm²
95 mm²
95 mm²
Cabinet Modules
Manual, 03/2013, A5E03263538A