8.26 L10, dv/dt filter plus Voltage Peak Limiter
Table 8- 44
Table 8- 45
Commissioning
During commissioning, the dv/dt filter must be logged on using STARTER or via the AOP30
operator panel (p0230 = 2).
Note
Reset when establishing the factory setting
Parameter p0230 is reset when the factory setting is established. The parameter has to be
reset when recommissioning.
470
Maximum permissible motor cable lengths for the DC link voltage 510 - 720 V DC
Frame sizes FX, GX, HX
Shielded cable max. 300 m or
unshielded cable max. 450 m
6SL3720-1TE32-1AAx
6SL3720-1TE32-6AAx
6SL3720-1TE33-1AAx
6SL3720-1TE33-8AAx
6SL3720-1TE35-0AAx
6SL3720-1TE36-1AAx
6SL3720-1TE37-5AAx
6SL3720-1TE38-4AAx
Maximum permissible motor cable lengths for the DC link voltage 675 - 1035 V DC
Frame sizes FX, GX, HX
Shielded cable max. 300 m or
unshielded cable max. 450 m
6SL3720-1TG28-5AAx
6SL3720-1TG31-0AAx
6SL3720-1TG31-2AAx
6SL3720-1TG31-5AAx
6SL3720-1TG31-8AAx
6SL3720-1TG32-2AAx
6SL3720-1TG32-6AAx
6SL3720-1TG33-3AAx
6SL3720-1TG34-1AAx
6SL3720-1TG34-7AAx
6SL3720-1TG35-8AAx
Frame size JX
Shielded cable max. 150 m or
unshielded cable max. 225 m
6SL3720-1TE41-0AAx
6SL3720-1TE41-2AAx
6SL3720-1TE41-4AAx
-
-
-
-
-
Frame size JX
Shielded cable max. 150 m or
unshielded cable max. 225 m
6SL3720-1TG37-4AAx
6SL3720-1TG38-1AAx
6SL3720-1TG38-8AAx
6SL3720-1TG41-0AAx
6SL3720-1TG41-3AAx
-
-
-
-
-
-