Activation Of Actuators / Vsd; Lmv51; Lmv52; Number Of Fuel Actuators - Siemens LMV5 Series Basic Documentation

Burner control with integrated fuel / air ratio control, burner control with load control and oxygen trim control for forced-draft burners
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Activation of
actuators / VSD

LMV51...

LMV52...

Number of fuel actuators

Note

Traveling times

Shutdown behavior

Overload protection
of actuators

Curve adjustment

Siemens Building Technologies
HVAC Products
Parameters:
AuxActuator (deactivated / activated)
VSDOperation
AirActuator (deactivated / activated) (air influen)
AuxActuator 1 (deactivated / activated) (air influen)
AuxActuator 2 (deactivated / activated) (air influen)
AuxActuator 3 (deactivated / activated) (air influen)
VSD (deactivated / activated)(air influen)
If the auxiliary actuator is not required, it must be deactivated. This can be selected
separately for both types of fuel. Here, with the LMV51.2..., the VSD will be activated.
The required actuators must be activated. If O2 trim control is used, the actuators
having an impact on the air volume must be parameterized to «air influen».
The standard LMV5... system uses 1 fuel actuator for gas and 1 fuel actuator for oil. But
it is also possible to use one common actuator for the fuel damper and the oil pressure
controller.
However, it is still possible to parameterize independent curves for both types of fuel.
Parameter:
NumFuelActuators (1 / 2)
If the above mentioned parameter was set to «1», the common fuel actuator must be
addressed as a «gas actuator».
The traveling speed of the actuators can be adjusted for the different burner statuses.
The time to be parameterized is the period of time the actuator requires to cover an
angular rotation of 90°.
Traveling speed in the phases with no flame (e.g. traveling to prepurge):
Parameter:
TmeNoFlame
Traveling speed in the operating position in modulating operation:
Parameter:
OperatRampMod
Traveling speed in the operating position in multistage operation:
Parameter:
OperatRampStage
When parameterizing the speeds, the running times of the connected actuators must be
taken into consideration.
The positions the actuators assume in the event of lockout can be adjusted. To
facilitate fault diagnostics, the actuators can be stopped at their last position or can be
driven to their home or postpurge position.
Parameter:
ShutdownBehav (Unchanged / PostpurgeP / HomePos)
If the actuators block, lockout will be enforced.
However, if the actuators cannot reach the positions required by lockout, they would be
damaged due to overtemperatures.
To prevent this, the actuators will be deactivated after a maximum time of 35 seconds,
or at 20 % above the value for TmeNoFlame parameterized.
Refer to chapter «Displays and settings» / special function curve adjustment FARC.
Basic Documentation LMV51...
5 Fuel / air ratio control (FARC)
LMV51...
LMV52...
x
x
LMV51.2...
x
x
x
x
x
65/278
CC1P7550en
01.10.2003