Replacing A Direct-Current Power Cooling Module Battery In A Controller Node; Enclosure-Sp 5.X - HPE 3PAR StoreServ 8000 Service And Upgrade Manual

Hide thumbs Also See for 3PAR StoreServ 8000:
Table of Contents

Advertisement

c. Tighten the clamp.
d. Move the power switch to the on position.
Verification
13. Verify that the AC PCM has been successfully installed by the LEDs.
Confirm that the PCM OK LED is solid green.
14. Stop the Locate action on the drive enclosure.
At the right side of the Schematic view of the drive enclosure, click the UID icon.
15. After the component replacement, initiate Check Health on the storage system.
a. From the Service Console interface, select Systems.
b. Select Actions > Check health.
16. If significant time is left in the maintenance window, end the Maintenance Mode.
a. From the Service Console interface, select Systems.
b. Select Actions > Set maintenance mode.
c. To end the maintenance window associated with the replacement, click X.
The flow of support information and local notifications of system alerts will be sent to Hewlett
Packard Enterprise again.
17. Follow the return instructions provided with the replacement component.
Replacing a direct-current power cooling module battery in a controller
node enclosure—SP 5.x
This procedure is for the replacement of a battery in an -48V direct-current (DC) power cooling module
(PCM) in the controller node enclosure using HPE 3PAR Service Processor (SP) 5.x. The battery can be
replaced without replacing the entire PCM.
WARNING: Since there is a risk of injury from electric shock or high energy levels, only a certified
electrician who knows about the procedures, precautions, and hazards associated with direct-
current (DC) power should perform the power wiring, cabling, routine maintenance, and service of a
storage system installed in a direct-current power environment. Hewlett Packard Enterprise and
partner service personnel are not authorized to perform DC power wiring or cabling.
CAUTION: Connecting to a direct-current power source outside the designated -48V DC nominal
range (-36V DC to -72V DC) may damage the direct-current power cooling module.
IMPORTANT: The direct-current components are qualified and supported only with a direct-current
HPE 3PAR StoreServ 8000 Storage system running HPE 3PAR OS 3.3.1 and later versions.
IMPORTANT: The storage system ordered for installation in a direct-current (DC) power
environment requires the installation of DC-specific components. Use of components with
alternating-current (AC) power in the DC storage system is prohibited.
36
Service

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents