Point Program
3.4.7 Annunciator Board Label
When
A C S B O A R D
Soft Keys
A C S L A B E L :
3.4.8 Audio Point Programming
When DVC or DAA is selected from the Point Program menu, the Audio Volume Control menu
appears.
Soft Keys
MASTER VOLUME: - This field can set the volume for all audio outputs at the DVC node. When
the audio amplifier point is set to 00, as it is in Figure 3.43, the setting affects all audio outputs on
the DVC node (this includes all outputs on its DAAs). When a specific DAA point is entered at the
point program menu (for example, N078AA01) the MASTER VOLUME setting will apply to the
audio outputs at that DAA ( the DAA with its address set to 01). Set this field to any volume
setting from 0 (off) to 15 (high). Default: 15
NFS2-3030 Programming Manual — P/N 52545:A 11/29/2005
is selected from the Point Program Menu, the ACS Label Menu appears.
A C S B O A R D P R O G R A M M I N G
A C S L A B E L :
E A S T W I N G S P E A K E R S
Figure 3.42 ACS Label Menu Screen
Type a label for the selected annunciator. The label can have up to 40 characters.
A U D I O V O L U M E C O N T R O L
P O I N T : N 0 7 8 A A 0 0
M A S T E R V O L U M E : 9
A U X I L I A R Y V O L U M E : 1 2
Figure 3.43 Audio Point Programming Menu Screen
A 0 1
A C C E P T
A C C E P T
Program
B A C K
B A C K