Section 2: Commissioning and
handover

View zone information

Display zones (
21 ent

Walk test

1.
Select Test All Zones (
to perform a silent test, press
It is possible to walk test selected zones only. Refer to Walk Test [31].
2.
Activate each zone in turn.
Note: If you do not activate any zone for 20 minutes the test will stop automatically.
3.
To end the test, press
Walk test results
To view the results of your walk test, select Display Log (

Test outputs

Outputs are tested by function, for example Bells or Strobe.
1.
Select Outputs (
2.
Press
or
to move to the output you wish to test, or type its number.
A
B
3.
Press
to test the selected output device.
ent
4.
Press
to stop the test.
ent
5.
Repeat steps 2 to 4 to select and test other outputs.
6.
Press
to exit the Test Output function.
esc

Diagnostic test (optional)

Check the Latest (
61 ent 1 ent
Modules
PSU
baseline record
). View information about any selected zone.
31 ent 2 ent 2 ent 1
31 ent 2 ent 1 ent 1
.
esc
). 01=Bells is displayed on the keypad.
32 ent
) and Historical (
View zone information
) to perform an audible test. Alternatively,
.
).
22 ent
) status of:
61 ent 2 ent
33