Honeywell Galaxy Flex V3 Series Installer Manual page 187

Table of Contents

Advertisement

Galaxy Flex Installer Manual
Note: Each MAX card can be assigned a single menu function (refer to Codes [42]).
Activating this function with a card that is assigned to all groups, on a MAX that is
only assigned to a single group, results in the function operating on all of the card's
groups. The MAX function is not restricted to the groups assigned to the MAX, it is
restricted to the groups assigned to the card, as long as there is one group common
to both.
This means that a MAX assigned only to group 1, for example, can be used to activate the
MAX function on groups 1, 2, 3 and 4 by a card with all of these groups allocated. The
groups are assigned to the MAX card using Codes [42].
In access mode, access will be granted if there are common groups between the card and the
MAX reader and all the groups assigned to the card are unset. For the card held function, the
groups affected by the function will be all the groups assigned to the card, so long as there is
at least one common group between the card and the MAX.
Common Group Restriction
To enhance group restrictions press
limits the operation described in the paragraph above only to groups which are common to
both the MAX and the card.
Refer to the following table for examples of how the readers respond to different situations
with the Common Group Restriction on and off. The card held function used in the example
is Timed Set.
Situation at time of card swipe
All groups unset
All groups set
Common groups unset and one or
more groups on card set
One or more common groups set,
other groups unset
Assigning Groups to Group Restriction
When you select the option the groups currently allocated to the MAX are displayed. Press
the group number to toggle the group assigned to the MAX.
When you have assigned the required groups to the user, press ent.
Emergencies [69.2.2.5]
Use this option to configure each individual MAX to respond to fire zones in a given set of
groups. When a fire zone is opened in one of the groups allocated to the MAX, the MAX
triggers the door strike and holds the door open until the system is reset. All the MAX LEDs
light and the buzzer sounds. Closing the fire zone has no effect; MAX units are treated as
latched outputs and an appropriate level reset is required. Reset occurs immediately when
applied.
when assigning groups in Group Restriction. This
Action on card held
No
All groups on card start to set
All groups on card are unset
Groups on card are unset
All groups on card are unset
Access Control [69]
on Group Restriction
All common groups start to set
All common groups are unset
Common groups are set
All common groups are unset
187