Galaxy Flex Installer Manual
Inputs
The DCM includes the following sensing inputs:
Door Contact (DC)
This input is a normal alarm zone input that has the same functionality
as a normal security zone type. It uses normal 1 k/2 k double balanced
zone wiring.
Request To Exit Contact (EC)
This input is a normally open contact. When activated it allows the
door to unlock for the programmed duration. Additionally, the door
can be held unlocked indefinitely by holding the EC closed. In this
case, the relay activates only for the programmed duration but the door
propped alarm is held off. This can be achieved, for example, by using
a keyswitch wired in parallel with the normal EC button.
Function Contact
This uses normal 1 k/2 k double balanced zone wiring. It initiates a
pre-programmed menu option following a valid card. The normal use
is to activate the setting procedure via the reader but any menu option
can be programmed.
Tamper Inputs
The tamper circuits for both readers should be wired to the same
tamper terminals on the DCM. The two circuits are wired in parallel,
each with its own series resistor as follows:
The reader tamper is double-balanced.
Reader 1 – 5.6 k
Reader 2 – 12 k
Appendix G: Peripherals
door contact
request to exit
function contact
tamper contact