Program Zones [52]
01 Final
Zones programmed as Final initiate the unsetting procedure and terminate setting procedure;
opening the Final zone when the system or group is set starts the entry timer; opening and
then closing the Final zone during the exit procedure sets the system or assigned groups,
providing all the zones are closed. The opening (+) and closing (–) of Final zones during the
setting and unsetting procedures are recorded in the event log.
Pressing
when programming a Final zone doubles the entry time of the group.
Opening a Final zone during the exit time is reported on the keypad as an open zone; the
entry/exit horns bleep rapidly to indicate that the zone is open.
Note: The termination feature of a Final zone can be extended to terminate the setting of
multiple groups by pressing
Group Function.
02 Exit
Zones that protect the entry and exit routes are programmed as Exit. During the setting and
unsetting procedures Exit zones have a non-alarm operation. If the Exit zone is activated
while the system is set, without the unsetting of the group being initiated, an Intruder alarm
condition is activated.
Opening an Exit zone during the exit time is reported on the keypad as an open zone; the
entry/exit horns bleep rapidly to indicate that the zone is open.
Note: The Exit zone can be assigned to multiple groups by pressing
group to the zone. This allows an Exit zone to be activated in a group which is not
currently being unset without activating an Intruder alarm. Refer to the Star
Function.
03 Intruder
The Intruder function is inactive when the system is unset. When the system is set,
activation of an Intruder zone causes a full alarm activation that requires to be reset with a
code authorized for System Reset (refer to System Reset [51.6] and Reduce Reset
[51.55.3]).
All zones are programmed as Intruder by default, including the zones on RIOs that are
added to the system at a later date.
05 Security
The Security zone function is continuously operational, except that a Security zone
activation when the system is unset generates a local alarm (Horn outputs activated) that
does not require a system reset. Any valid code (type 2 or above) cancels the alarm and
resets the system. An activation in the set state generates a full alarm that requires a system
reset. The activation (+) and restoration (–) of Security zones is recorded in the event log.
07 Entry
This function initiates the unsetting procedure in the same way as a Final zone. However,
during the setting routine an Entry zone operates as an Exit zone type. This function is