Honeywell Galaxy Flex V3 Series Installer Manual page 165

Table of Contents

Advertisement

Galaxy Flex Installer Manual
1=Low Sig Level
2=Noise Level
3=Low Battery
Diagnostic log [61.4]
To help you trace intermittent faults this event log records minor failures and degradations
in performance, for example a lower than normal signal strength or a higher than normal
zone resistance. Each event is recorded with the hours, minutes and seconds. The # key can
be used to display further information for certain events where available. The following list
shows the events which can be recorded in the diagnostic log:
SSC:
Change in Signal Strength consistency for wireless sensors
MIF:
Missed frame of supervision message from a wireless device. This is when
one expected supervision message is not received but before the overall
supervision time expires.
NOL:
Change in the background noise level at an RF Portal
RSSI LO:
GSM signal level has dropped below the minimum for more than one minute
RSSI OK:
GSM signal level has restored to normal level
NO GSM:
GSM signal has been lost
NO GPRS:
No GPRS Network connection
GSM ERR:
GSM connection error
GSM OK:
GSM has connected to the Network successfully
PIN FIN:
SIM PIN failure – only one attempt left before lockout
PIN WPN:
GSM SIM card PIN registration is taking place
PIN BAD:
PIN for GSM SIM card is incorrect
PIN BLK:
SIM blocked due to wrong PIN
NO SIM:
No SIM card detected in the GSM module
LGN ERR:
GPRS log-in has failed – invalid APN
IP FAIL:
IP Check signal has failed to be received at ARC
IP RSTR:
IP Check signal has started working again
Diagnostics [61]