Honeywell Galaxy Flex V3 Series Installer Manual page 86

Table of Contents

Advertisement

Parameters [51]
If a valid code is entered within the programmed abort time:
If an abort output/channel is allocated to the alarmed group:
– The Abort signal is sent.
– The intruder condition is not restored.
– Intruder restore is not signalled.
If there is no abort output allocated to the alarmed group:
– The intruder condition is restored.
– Intruder restore is signalled.
If the programmed abort time is allowed to expire without a valid code being entered,
then the system requires a system reset. The panel cannot be set until this occurs.
Note: If Reduced Resets [51.55.3] is enabled, the alarm is reset by the user code when the
alarm is unconfirmed.
Modified Abort Operation
The abort operation can be modified by adding a
Adding
alters the standard operation so that the signalling of the intruder condition is
#
delayed until the end of the abort time. If the system is unset during the entry time or
abort time, no alarm condition is signalled.
Adding * alters the standard operation so that if a user strays from the entry route
within the entry time the abort timer will start immediately. The intruder alarm will be
signalled at the end of the abort timer as long as the entry time has expired. A 2nd
intruder activation after the entry time will override the abort timer.
Notes:
1.
To comply with PD6662 2010, the
to 30 seconds.
2.
To comply with EN50131:2004 and DD243:2004, the # abort operation must be used
with Abort Time set to 30 seconds or longer.
Bell Delay [51.03.2]
Use this option to hold off the start of any bell delay time programmed in parameter 51.02
until the end of the abort time programmed above.
Exit Time [51.04]
This option has two sub options:
1=Entry time (for full set and part set)
2=Night exit (for night set only)
Use this option to program the time allowed to leave the premises via the exit route before
the system sets. The default is 120 seconds and the range is 0 to 300 seconds.
86
Galaxy Flex Installer Manual
or
to the programmed time.
#
abort operation must be used with Abort Time set

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Galaxy flex 20 v3Galaxy flex 50 v3Galaxy flex 100 v3

Table of Contents