About the VISTA-128BPEN
The VISTA-128BPEN is an 8-partition, UL Listed control panel with the following features:
•
Supports hardwired, polling loop, and wireless zones
•
Supervision of bells, keypads, RF receivers, and output devices
•
Scheduling capabilities (allows certain operations to be automated
ULC
Scheduling is currently not approved for ULC applications.
•
The capability to link up to eight control panels using Panel Linking Modules
The VISTA-128BPEN can interface with the following devices:
•
An alpha numeric paging device (VA8201)
•
SYMPHONY (AUI)
•
Panel Link Module (VA8200)
•
Voice Keypad (6160V)
•
An ECP Communicator that can send Contact ID messages
•
An access control system by using either the ADEMCO PassPoint system (via the VISTA Gateway Module) or a
VistaKey module (via the polling loop)
U L
The access control function is not Listed for use with the VISTA-128BPEN Control Panel in a UL installation.
The system supports either the VistaKey or the VISTA Gateway Module, not both.
Features
Hardwire and Optional Expansion Zones
•
Provides nine hardwire zones.
•
Supports up to 16 2-wire smoke detectors on zone 1.
•
Automatically resets 4-wire smoke detectors using the J7 output when a code + off is entered.
•
Triggers the built-in sounders on other hardwired smoke detectors if one smoke detector annunciates an alarm. This
feature requires a 4204 Relay Module.
•
Provides tamper supervision on the hardwire zones.
•
Supports up to 50 2-wire latching glassbreak detectors on zone 8.
•
Supports up to 119 additional expansion zones using a built-in polling (multiplex) loop.
•
Supports up to 127 wireless zones (fewer if using hardwire and/or polling loop zones).
The 5881ENHC RF Receiver, 5869 Holdup Switch Transmitter and 5817CB Wireless Commercial Household
U L
Transmitter are listed for UL Commercial Burglary applications. All other RF receivers and transmitters are not listed
for UL Commercial Burglary applications.
•
Can program burglary zones as silent in the alarm condition (alarm output is silent and the keypad does not display
or sound the alarm).
•
Provides three keypad panic keys: 1 + ✴ (A), ✴ + # (B), and 3 + # (C).
General Description
S E C T I O N
1
1-1