Galaxy Flex Installer Manual
01 Bells (Latch)
This output is activated on a full alarm event when the system is set, and is subject to the
Bell Time, Bell Delay and No. Re-arm parameters.
02 Strobe (Latch)
This output is activated on a full alarm event during the set state, and is subject to the Bell
Delay. It follows the Bell Time, but latches on after the last re-arm.
03 PA (Latch)
This output is activated whenever any of the PA zone types activate. The output is not
subject to the Re-arm parameter. It latches on and remains active until a valid code, with the
appropriate PA Reset level, is entered.
04 Intruder (Latch)
This output is activated on a full alarm event during the set state. Depending on the
programming of Force Restore [51.56], the intruder output restore is either subject to the
Confirm Time Window + unset or entry of a valid code with the appropriate system reset
level. Refer to the Force Restore [51.56] description for more information.
05 Tamper (Latch)
The Tamper output is activated whenever a circuit tamper or lid tamper occurs. The output
is not subject to the Re-arm parameter. It latches on and remains active until a valid code,
with the appropriate Tamper Reset level, is entered. The output is also activated on the first
entry of the engineer code when accessing engineer mode.
Note: The Tamper output is not activated when engineer access is authorized by the user.
07 Reset (Latch)
This output is used as a control line output to latch, freeze and reset movement detector
LEDs.
08 Switch DC (Pulse)
This output is used to power detectors that require a momentary power interruption to reset
them, for example, break glass or vibration detectors. It reverses its polarity (changes from
0 V to 12 V) for the period of the Pulse output mode when the setting procedure has been
initiated.
Note: When wiring detectors to a Switch d.c. output, connect the positive lead of the
detector to the 12 V terminal of a power supply and the negative lead to the Switch
d.c. output terminal. Do not change the Output Polarity to 1=Neg.
09 Set (Reflex)
The Set output is activated when the assigned groups on the system are set. It is a Reflex
output and follows the set and unset status of the groups.
Program Outputs [53]
127