Outputs [32]

Note: PA, PA Silent, PA Delay, PA Silent Delay and Fire are not included in the test when
is used to include all zones. The response time of the zone circuits is reduced to
20 ms (40 ms for RF RIOs) for the duration of the walk test to detect loose
connections or damaged wiring.
Once the walk test has started, opening a zone (or a zone that is open at the start of the test)
activates outputs programmed as entry/exit horn. If a single zone is open, the keypad
displays the address and function of the zone. If multiple zones are open, the keypad
displays how many zones are open. Use
Note: The Walk Test option does not display the status of the zones. If an open zone is
included in the walk test, the entry/exit horn activates as soon as the test is started
and remains active until the zone is closed.
While the walk test is active the message WALK TEST ACTIVE / ESC to abort is
displayed.
Press
to view all zones that have been walk tested so far.
#
To return to the walk test, press
Note: RF zones also record the signal strength in reduced gain mode.
End the walk test
To end the walk test, press
The test ends automatically if no zones are activated for 20 minutes.
To view the results of the test, access the event log (refer to Display Log [22]). The start of
the walk test is indicated by the WALK TEST + message. Each tested zone is recorded (the
activation of each zone is recorded only once during the test, even if it was opened several
times). The end of the test is indicated by WALK TEST –.
Outputs [32]
Outputs are tested by function: for example, when you select 01=BELLS, all outputs
programmed as Bells are activated. Refer to Program Outputs [53] for a full description of
each output function.
When you enter the Outputs option, output function type 01=BELLS is offered for
selection.
Press
or
to move to the required output function type, or enter the function type number
A
B
directly. For example enter
To test the selected output function press
as required.
Users
User types 5 and 6 have access to 01=BELLS and 02=STROBE only in the Output option.
Only the engineer has access to all the output types.
58
or
A
B
again.
#
.
esc
to select SECURITY.
13
. Press
ent
Galaxy Flex Installer Manual
to view the open zones.
to toggle the function ON and OFF
ent