8.15.17 RESET NOT (RN)
January 2012
Syntax:
RN (RESET NOT)
Operands:
M, I, O, T, C
Action:
If the logic accumulator = 0, then set the addressed operand to 0, otherwise
do not change it. Use the RN command at the end of a sequence of logical
gating operations in order to influence an operand depending on the result of
gating. This command can be used several times in succession (see example).
Example:
Gate input I4 and I5 with OR. If the gating result is 0, then reset output O2 and
marker M500.
Initial state:
Input
I4
= 0
Input
I5
= 0
Output
O2
= ?
Marker
M500 = ?
Function
Load the operand content
into the logic
accumulator.
Gate the content of the
logic accumulator and
input I5 with OR.
Since the result of the
operation is 0, reset
output O2.
Since the result of the
operation is 0, reset
marker M500.
8.15 Command Set
STL
Accumulator
content
L I4
0
O I5
0
RN O2
0
RN
0
M500
Operand content
0
0
0
0
1677