8.4.4 Fast PLC inputs
1532
Settings in the configuration editor
System
PLC
CfgPlcFastInput
number
significance
operand
With CfgPlcFastInput, you define the PLC inputs that are interrogated within
the position controller cycle time (see "MP_ipoCycle" on page 1481) instead of
within the defined PLC cycle time (see "MP_plcCount" on page 1481). In
MP_number, enter the PLC input of the control that is to be used as a fast PLC
input. You define the associated symbolic PLC operands set by the fast PLC
input in MP_operand.
A maximum of five PLC inputs can be defined as fast PLC inputs. For this
purpose, five input arrays [arrays 0...4] are available in the configuration editor
of the control.
For the control to identify with certainty a signal change, the signal duration at
the fast PLC input must last a minimum of 4 ms.
Warning
Only the PLC inputs of the control can be defined as fast PLC inputs, and
not the inputs on a PL 510.
MP_number
Numerical designation for fast PLC inputs
Available from NCK software version: 597 110-01.
Format:
Array [0...4]
Input:
0 to 31 [no. of the PLC input on the MC]
Default:
0
Access:
LEVEL3
Reaction:
RUN
HEIDENHAIN Technical Manual MANUALplus 620
MP number
103701
103702
103703