Connecting To Hmi Adapter - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal (non-mitsubishi electric products 2)
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

15.2.6

Connecting to HMI Adapter

■1. Communication settings
The following communication settings are made at the communication detail settings of the GOT side.
For details, refer to the following.
15.2.4 ■2. Communication detail settings
Transmission speed
Data bit
Parity bit
Stop bit
Adapter address
Host address
15.2.7
Connecting to SIMATIC S7-200, SIMATIC S7-200 CN/SMART
The following devices are available to GT21 and GS21.
■1. Communication settings
Set the communication settings of PLC and PC/PPI cable.
(1) PLC settings
Set the communication settings of PLC by operating the SIEMENS programming tool(STEP7-WIN32).
*1
Transmission speed
Data bit
Parity bit
Stop bit
*2
Host address
*1
Adjust the settings with GOT settings.
*2
Set the address without overlapping the address of other units.
Setting item
Setting item
PLC side setting
9600bps, 19200bps, 38400bps
8bits (fixed)
Odd (fixed)
1bit (fixed)
1 to 31
1 to 31
PLC Side Setting
9600bps, 19200bps
8bits (fixed)
Even (fixed)
1bit (fixed)
1 to 31
15.2 Serial Connection
15
15 - 11