■2. Communication detail settings
Make the settings according to the usage environment.
Item
GOT Net No.
*1
GOT Station
GOT Communication Port No.
Startup Time
Timeout Time
Delay Time
*1
Set different values for [GOT Station] of [Detail Setting] and [Station] of [Connected Ethernet Controller Setting].
➠
*2
When assigning the same driver to the multiple channels, in the communication drivers set as the second and following, the
default value of [GOT Communication Port No.] becomes the earliest number in the vacant numbers of No. 6000 and later.
■3. GOT Ethernet Setting
The GOT can be connected to a different network by configuring the following setting.
(1) GOT IP address setting
Set the following communication port setting.
• Standard port (When using GT25-W, port 1)
• Extension port (When using GT25-W, port 2)
(2) GOT Ethernet common setting
Set the following setting which is common to the standard port and the extension port, or port 1 and port 2.
• [Default Gateway]
• [Peripheral S/W Communication Port No.]
• [Transparent Port No.]
(3) IP filter setting
By configuring the IP filter setting, the access from the specific IP address can be permitted or shut off.
For the detailed settings, refer to the following manual.
➠
1.1.2 GOT Ethernet Setting
Set the network No. of the GOT.
(Default: 1)
Set the station No. of the GOT.
(Default: 18)
Set the GOT port No. for the connection with the Ethernet module.
(Default:)
Ethernet (SIEMENS S7), Gateway: 5023
Ethernet (SIEMENS OP), Gateway: 5024
Specify the time period from the GOT startup until GOT starts the
communication with the PLC CPU.
(Default: 3sec)
Set the time period for a communication to time out.
(Default: 3sec)
Set the delay time for reducing the load of the network/destination PLC.
(Default: 0ms)
■4. Connected Ethernet Controller Setting
POINT
POINT
POINT
(1) Communication interface setting by the Utility
The communication interface setting can be changed on the Utility's [Communication setting]
after writing [Communication Settings] of project data.
For details on the Utility, refer to the following manual.
➠
GOT2000 Series User's Manual (Utility)
(2) Precedence in communication settings
When settings are made by GT Designer3 or the Utility, the latest setting is effective.
Description
*2
*2
15.3 Ethernet Connection
Range
1 to 239
1 to 254
1024 to 5010, 5023 to 65534 (Except
for 5011, 5012, 5013, and 49153 to
4917)
3 to 255 sec
3 to 90 sec
0 to 10000 (ms)
15 - 17