■2. Communication detail settings
Make the settings according to the usage environment.
Item
GOT Net No.
*1
GOT Station
GOT Communication Port No.
Startup Time
Timeout Time
Delay Time
*1
Set different values for [GOT Station] of [Detail Setting] and [Station] of [Connected Ethernet Controller Setting].
*2
When assigning the same driver to the multiple channels, in the communication drivers set as the second and following, the
default value of [GOT Communication Port No.] becomes the earliest number in the vacant numbers of No. 6000 and later.
■3. GOT Ethernet Setting
The GOT can be connected to a different network by configuring the following setting.
(1) GOT IP address setting
Set the following communication port setting.
• Standard port (When using GT25-W, port 1)
• Extension port (When using GT25-W, port 2)
(2) GOT Ethernet common setting
Set the following setting which is common to the standard port and the extension port, or port 1 and port 2.
• [Default Gateway]
• [Peripheral S/W Communication Port No.]
• [Transparent Port No.]
(3) IP filter setting
By configuring the IP filter setting, the access from the specific IP address can be permitted or shut off.
For the detailed settings, refer to the following manual.
1.1.2 GOT Ethernet Setting
Set the network No. of the GOT.
(Default: 1)
Set the station No. of the GOT.
(Default: 18)
Set the GOT port No. for the connection with the Ethernet module.
(Default:)
Ethernet (SIEMENS S7), Gateway: 5023
Ethernet (SIEMENS OP), Gateway: 5024
Specify the time period from the GOT startup until GOT starts the
communication with the PLC CPU.
(Default: 3sec)
Set the time period for a communication to time out.
(Default: 3sec)
Set the delay time for reducing the load of the network/destination PLC.
(Default: 0ms)
■4. Connected Ethernet Controller Setting
POINT
POINT
POINT
(1) Communication interface setting by the Utility
The communication interface setting can be changed on the Utility's [Communication setting]
after writing [Communication Settings] of project data.
For details on the Utility, refer to the following manual.
GOT2000 Series User's Manual (Utility)
(2) Precedence in communication settings
When settings are made by GT Designer3 or the Utility, the latest setting is effective.
Description
*2
*2
15.3 Ethernet Connection
Range
1 to 239
1 to 254
1024 to 5010, 5023 to 65534 (Except
for 5011, 5012, 5013, and 49153 to
4917)
3 to 255 sec
3 to 90 sec
0 to 10000 (ms)
15 - 17