Mitsubishi Electric GOT2000 Series Connection Manual page 341

Graphic operation terminal (non-mitsubishi electric products 2)
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

(4) RS-232 connection diagram 4)
*1
For the terminal number of the temperature controller, refer to the following table.
■2. Precautions when preparing a cable
(1) Cable length
The length of the RS-232 cable must be 15m or less.
(2) GOT side connector
For the GOT side connector, refer to the following.
1.4.1 GOT connector specifications
(3) RKC temperature controller side connector
Use the connector compatible with the RKC temperature controller side module.
For details, refer to user's manual of the RKC temperature controller side.
RKC temperature controller side
GOT side
CD
1
RD(RXD)
2
SD(TXD)
3
ER(DTR)
4
SG
5
DR(DSR)
6
RS(RTS)
7
CS(CTS)
8
-
9
Signal
FB400
name
FB900
SG
25
SD(TXD)
26
RD(RXD)
27
(Modular connector) * 1
SD(TXD)
RD(RXD)
SG
Terminal No.
HA400/401
PF900
HA900/901
PF901
Communication 1
Communication 2
25
13
26
14
27
15
9.3 Connection Diagram
MA900
MA901
25
44
26
45
27
46
9 - 35