Connecting To Ic697Cmm711 - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal (non-mitsubishi electric products 2)
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

11.5.4

Connecting to IC697CMM711

■1. Communication settings
Make the communication settings using the engineering tool.
When making the settings, set [Configuration Mode] on the [Setting] tab of the engineering tool to "SNP only".
*1
SNP Enable
*2
SNP Mode
*3
Interface
Data Rate
Parity
Stop Bits
*4
Flow Control
*5
Turn Around Delay
*6
Timeout
*1
*2
*3
*4
*5
*6
11.5.5
Station number setting
Set each station number so that no station number overlaps.
The station number can be set without regard to the cable connection order. There is no problem even if station numbers
are not consecutive.
■1. Direct specification
Specify the station No. of the PLC to be changed when setting device.
11 - 16
11.5 PLC Side Setting
Setting item
Set to YES.
Set to SLAVE.
Set the communication format to be used.
(only when connecting to Port2)
Set to NONE.
Set to NONE.
Set to LONG.
Station
No.3
GOT
Examples of station number setting
POINT
POINT
POINT
PLC Station No. settings
Make sure to set a 2-digit number for the station No. of the PLC to be monitored by the GOT.
YES
Slave
RS232, RS485
9600bps, 19200bps
ODD, NONE, EVEN
1bit, 2bits
NONE
NONE
Long
Station
Station
Station
No.6
No.00
No.15
Specification range
00 to 31
PLC side setting