Connecting To Versamaxmicro - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal (non-mitsubishi electric products 2)
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

11.5.2

Connecting to VersaMaxMicro

■1. Communication settings
Make the communication settings using the engineering tool.
Data Rate
*6
Bits / Character
Parity
Stop Bits
*1
Port Mode
*2
Port Type
Flow Control
*3
Timeout
*4
Turn Around Delay
*5
SNP ID
*1
Set to the SNP protocol.
*2
Set to Slave.
*3
Set to Long.
*4
Set to 0.
*5
Set within the range of 00 to 31.
When specifying the station No. from 0 to 9, add "0" before the number and set it as 00 to 09.
*6
Set the same set value for the data length for the GOT and PLC.
11.5.3
Connecting to IC693CMM311
■1. Communication settings
Make the communication settings using the engineering tool.
When making the settings, set [Configuration Mode] on the [Setting] tab of the engineering tool to "SNP only".
*1
SNP Enable
*2
SNP Mode
*3
Interface
Data Rate
Parity
Stop Bits
*4
Flow Control
*5
Turn Around Delay
*6
Timeout
*1
Set to YES.
*2
Set to SLAVE.
*3
Set the communication format to be used.
(only when connecting to Port2)
*4
Set to NONE.
*5
Set to NONE.
*6
Set to LONG.
Setting item
Setting item
PLC side setting
9600bps, 19200bps,
38400bps
7bits, 8bits
EVEN, ODD, NONE
1bit, 2bits
SNP
Slave
NONE
Long
0
00 to 31
PLC side setting
YES
Slave
RS232, RS485
9600bps, 19200bps
ODD, NONE, EVEN
1bit, 2bits
NONE
NONE
Long
11.5 PLC Side Setting
11
11 - 15