8.3
Connection Diagram
The following diagram shows the connection between the GOT and the temperature controller.
8.3.1
RS-232 cable
■1. Connection diagram
(1) RS-232 connection diagram 1)
*1
■2. Precautions when preparing a cable
(1) Cable length
The length of the RS-232 cable must be 15m or less.
(2) GOT side connector
For the GOT side connector, refer to the following.
➠
(3) YOKOGAWA temperature controller side connector
Use the connector compatible with the YOKOGAWA temperature controller side.
For details, refer to the user's manual of the YOKOGAWA temperature controller.
8 - 14
8.3 Connection Diagram
GOT side
CD
1
RD(RXD)
2
SD(TXD)
3
ER(DTR)
4
SG
5
DR(DSR)
6
RS(RTS)
7
CS(CTS)
8
-
9
Connect FG grounding to the appropriate part of a cable shield line.
1.4.1 GOT connector specifications
RS232C/RS485
Interface converter side
(ML2-□)
* 1
CD
1
RD
2
SD
3
ER
4
SG
5
DR
6
RS
7
CS
8
-
9