Mitsubishi Electric GOT2000 Series Connection Manual page 218

Graphic operation terminal (non-mitsubishi electric products 2)
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

■2. Settings by DIP switch
(1) Settings for 218TXB
Set the DIP switch (SW2) as follows.
N/O
*1
-
10/100
F/H
INIT
*2
TEST
*1
*2
6 - 36
6.3 Ethernet Connection
Setting Item
Mode Selection
Not used
Transmission Speed
Transmission Mode
Initial Startup
Test
Turn off all the unused switches.
When even one of those switches is on, the PLC may not normally operate.
When the PLC is started with the TEST switch on, the module starts the self-diagnosis and may not perform the communication.
Turn off the switch before the communication is started.
N/O
-
10/100
F/H
-
-
INIT
TEST
OFF
ON
Set value
ON: Extended mode (13 channels, up to 1024 words)
ON
OFF: Basic mode (10 channels, up to 512 words)
OFF
ON :10Mbps
OFF
OFF :100Mbps
ON: Full duplex mode
OFF
OFF: Half duplex mode
ON: Start up by the default IP address and the engineering port
No.
OFF
OFF: Start up by the IP address and the engineering port No. set
for CP-717
ON: The module starts the self-diagnosis when the PLC is started.
OFF
OFF: The module does not start the self-diagnosis when the PLC
is started.
Setting range
-