Connecting To Srj Series - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal (non-mitsubishi electric products 2)
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

9.5.5

Connecting to SRJ Series

■1. Communication settings
Communication settings are set with a RKC peripheral tool "PROTEM 2".
Item
Communication protocol
Communication speed
Interval time
■2. Rotary switch setting
Set the device address using the rotary switch for address setting.
Rotary switch for address setting
For address setting of master device and slave device, set as follows.
Address of master device
0
4
8
C
*1
J-TI-A/B is available to connect three slave devices for one master device.
9.5.6
Connecting to CB Series
■1. Communication settings
Item
*1
Device address
*2
Communication speed
Data bit configuration
Interval time
*1
When the setting value is set to 0, a communication is not made.
*2
Adjust the settings with GOT settings.
■2. Communication setting mode
Set the communication setting mode using the operation panel of the CB series main unit.
For details of the communication setting mode, refer to the following.
CB series "Communication Instruction Manual"
0: RKC communication
1: MODBUS
0: 19200bps
1: 38400bps
0 to 100ms
*1
Address range of slave device
1 to 3
5 to 7
9 to B
D to F
1 to 99
2: 9600bps
3: 19200bps
0: 8/1/None
6: 8/1/Even
7: 8/1/Odd
0 to 150
Setting range
1: MODBUS
Adjust the settings with GOT settings.
Set this as necessary.
Setting range
9.5 Temperature Controller Side Setting
Set value
9
9 - 59