11.5 PLC Side Setting

PLC CPU
Communication Modules
11.5.1
Connecting to Series 90-30
■1. Communication settings
Make the communication settings using the engineering tool.
When making the settings, set [Configuration Mode] on the [Setting] tab of the engineering tool to "SNP only".
*1
Port Mode
*2
Port Type
Data Rate
Flow Control
Parity
Stop Bits
*3
Timeout
*4
Turn Around Delay
*5
SNP ID
Converter Power Consumption
*1
*2
*3
*4
*5
*6
11 - 14
11.5 PLC Side Setting
POINT
POINT
POINT
GE PLC
For details of GE PLCs, refer to the following manuals.
GE PLC user's Manual
Model name
Series 90-30
VersaMaxMicro
IC693CMM311
IC697CMM711
Setting item
*6
Set to SNP.
Set to Slave.
Set to Long.
Set to 0.
Set within the range of 00 to 31.
When specifying the station No. from 0 to 9, add "0" before the number and set it as 00 to 09.
Set to 0.(only when connecting to Port2)
Refer to
11.5.1
11.5.2
11.5.3
11.5.4
PLC side setting
SNP
Slave
9600bps, 19200bps
NONE
EVEN, ODD, NONE
1bit, 2bits
Long
0
00 to 31
0