Mitsubishi Electric GOT2000 Series Connection Manual page 429

Graphic operation terminal (non-mitsubishi electric products 2)
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

(3) RS-422 connection diagram 3)
GOT side
SDA
1
SDB1
6
RDA
2
RDB
7
SG
5
RSA
3
CSA
4
RSB
8
CSB
9
*1
Connect FG grounding to the appropriate part of a cable shield line.
*2
Terminating resistor should be provided for a PLC which will be a terminal.
■2. Precautions when preparing a cable
(1) Cable length
The length of the RS-422 cable must be 1200m or less.
(2) GOT side connector
For the GOT side connector, refer to the following.
1.4.1 GOT connector specifications
(3) GE PLC side connector
Use the connector compatible with the GE PLC side module.
For details, refer to the GE PLC user's manual.
■3. Connecting terminating resistors
(1) GOT side
1) For GT27, GT25(Except GT2505-V) ,GT23
Set the terminating resistor setting switch of the GOT main unit to "Disable".
2) For GT2505-V
Set the terminating resistor selector to "330Ω".
For the procedure to set the terminating resistor, refer to the following.
1.4.3 Terminating resistors of GOT
(2) GE PLC side
When connecting a GE PLC to the GOT, a terminating resistor must be connected.
GE PLC user's Manual
PLC
RT
9
RD(B')
11
RD(A')
10
SD(B)
13
SD(A)
12
SG
7
RTS(A)
6
CTS(A')
15
RTS(B)
14
CTS(B')
8
SHLD
* 1
1
* 2
terminating resistor 120Ω
PLC
* 1
11.3 Connection Diagram
RT
9
RD(B')
11
RD(A')
10
SD(B)
13
SD(A)
12
SG
7
RTS(A)
6
CTS(A')
15
RTS(B)
14
CTS(B')
8
SHLD
1
11
11 - 11