Commissioning
5.3.6 Restoring Default Settings
NOTICE!
Risk of losing programming, motor data, localisation, and
monitoring records by restoration of default settings. To
provide a back-up, upload data to the LCP before initiali-
sation.
Restoring the default parameter settings is done by initiali-
sation of the frequency converter. Initialisation is carried
out through parameter 14-22 Operation Mode
(recommended) or manually.
•
Initialisation using parameter 14-22 Operation
Mode does not reset frequency converter settings,
such as operating hours, serial communication
selections, personal menu settings, fault log,
alarm log, and other monitoring functions.
•
Manual initialisation erases all motor,
programming, localisation, and monitoring data
and restores factory default settings.
Recommended initialisation procedure, via
parameter 14-22 Operation Mode
1.
Press [Main Menu] twice to access parameters.
2.
Scroll to parameter 14-22 Operation Mode and
press [OK].
Scroll to [2] Initialisation and press [OK].
3.
4.
Remove power to the unit and wait for the
display to turn off.
5.
Apply power to the unit.
Default parameter settings are restored during start-up.
This may take slightly longer than normal.
6.
Alarm 80 is displayed.
7.
Press [Reset] to return to operation mode.
Manual initialisation procedure
1.
Remove power to the unit and wait for the
display to turn off.
2.
Press and hold [Status], [Main Menu], and [OK] at
the same time while applying power to the unit
(approximately 5 s or until audible click and fan
starts).
Factory default parameter settings are restored during
start-up. This may take slightly longer than normal.
Manual initialisation does not reset the following frequency
converter information:
MG20MC22
Operating Instructions
•
•
•
•
5.4 Basic Programming
5.4.1 Commissioning with SmartStart
The SmartStart wizard enables fast configuration of basic
motor and application parameters.
•
•
•
NOTICE!
Motor data is required for the SmartStart set-up. The
required data is normally available on the motor
nameplate.
The SmartStart configures the frequency converter in 3
phases, each consisting of several steps, see Table 5.6.
1
Basic Programming
2
Application Section
3
Water and Pump Features
Table 5.6 SmartStart, Setup in 3 Phases
5.4.2 Commissioning via [Main Menu]
Recommended parameter settings are intended for start-
up and check-out purposes. Application settings may vary.
Enter data with power ON, but before operating the
frequency converter.
Danfoss A/S © 01/2015 All rights reserved.
Parameter 15-00 Operating hours.
Parameter 15-03 Power Up's.
Parameter 15-04 Over Temp's.
Parameter 15-05 Over Volt's.
SmartStart starts automatically, at first power up
or after initialisation of the frequency converter.
Follow the on-screen instructions to complete the
commissioning of the frequency converter.
Always reactivate SmartStart by selecting Quick
Menu Q4 - SmartStart.
For commissioning without use of the SmartStart
wizard, refer to chapter 5.4.2 Commissioning via
[Main Menu] or the programming guide.
Phase
Programme, for example
motor data
Select and programme
appropriate application:
•
Single pump/motor.
•
Motor alternation.
•
Basic cascade control.
•
Master/follower.
Go to water and pump
dedicated parameters.
5
Comment
27