Commissioning

5.3.6 Restoring Default Settings

NOTICE!
Risk of losing programming, motor data, localisation, and
monitoring records by restoration of default settings. To
provide a back-up, upload data to the LCP before initiali-
sation.
Restoring the default parameter settings is done by initiali-
sation of the frequency converter. Initialisation is carried
out through parameter 14-22 Operation Mode
(recommended) or manually.
Initialisation using parameter 14-22 Operation
Mode does not reset frequency converter settings,
such as operating hours, serial communication
selections, personal menu settings, fault log,
alarm log, and other monitoring functions.
Manual initialisation erases all motor,
programming, localisation, and monitoring data
and restores factory default settings.
Recommended initialisation procedure, via
parameter 14-22 Operation Mode
1.
Press [Main Menu] twice to access parameters.
2.
Scroll to parameter 14-22 Operation Mode and
press [OK].
Scroll to [2] Initialisation and press [OK].
3.
4.
Remove power to the unit and wait for the
display to turn off.
5.
Apply power to the unit.
Default parameter settings are restored during start-up.
This may take slightly longer than normal.
6.
Alarm 80 is displayed.
7.
Press [Reset] to return to operation mode.
Manual initialisation procedure
1.
Remove power to the unit and wait for the
display to turn off.
2.
Press and hold [Status], [Main Menu], and [OK] at
the same time while applying power to the unit
(approximately 5 s or until audible click and fan
starts).
Factory default parameter settings are restored during
start-up. This may take slightly longer than normal.
Manual initialisation does not reset the following frequency
converter information:
MG20MC22
Operating Instructions

5.4 Basic Programming

5.4.1 Commissioning with SmartStart

The SmartStart wizard enables fast configuration of basic
motor and application parameters.
NOTICE!
Motor data is required for the SmartStart set-up. The
required data is normally available on the motor
nameplate.
The SmartStart configures the frequency converter in 3
phases, each consisting of several steps, see Table 5.6.
1
Basic Programming
2
Application Section
3
Water and Pump Features
Table 5.6 SmartStart, Setup in 3 Phases

5.4.2 Commissioning via [Main Menu]

Recommended parameter settings are intended for start-
up and check-out purposes. Application settings may vary.
Enter data with power ON, but before operating the
frequency converter.
Danfoss A/S © 01/2015 All rights reserved.
Parameter 15-00 Operating hours.
Parameter 15-03 Power Up's.
Parameter 15-04 Over Temp's.
Parameter 15-05 Over Volt's.
SmartStart starts automatically, at first power up
or after initialisation of the frequency converter.
Follow the on-screen instructions to complete the
commissioning of the frequency converter.
Always reactivate SmartStart by selecting Quick
Menu Q4 - SmartStart.
For commissioning without use of the SmartStart
wizard, refer to chapter 5.4.2 Commissioning via
[Main Menu] or the programming guide.
Phase
Programme, for example
motor data
Select and programme
appropriate application:
Single pump/motor.
Motor alternation.
Basic cascade control.
Master/follower.
Go to water and pump
dedicated parameters.
5
Comment
27
5